Heavy fuel oil control depends on more than valve opening position. Viscosity, heat loss, available actuator torque, seat friction and position feedback all affect whether fuel reaches the boiler at a stable rate. In 2022, an anonymous thermal power producer in China asked Dombor to review an installation affected by flow variation, internal leakage and winter solidification.
The engineering response combined an electric actuated butterfly valve with body heat tracing, a polished flow path, reinforced PTFE seating and continuous position feedback. The result below is presented as a project-reported field case based on after-sales records and sales follow-up.
2022 Project Record
Customer: Anonymous thermal power producer
Application: Boiler heavy fuel oil control
Recorded medium condition: Approximately 120 cSt at 80°C
Valve configuration: 10-inch Class 150 electric actuated lug-type butterfly valve
Evidence basis: After-sales records and sales follow-up
Why Heavy Fuel Oil Control Was Unstable
The existing valves were working with a medium whose viscosity changed quickly as temperature fell. Project records show flow variation greater than ±15%, together with slow response, sticking and position drift. Local heat loss through the valve body could increase viscosity inside the flow path and, during winter operation, contribute to partial solidification. The customer reported three to four winter interruptions per year associated with this condition.
Seal life was a second problem. Resinous material accumulated around the sealing surfaces, increasing friction and accelerating seat wear. The previous valves typically developed internal leakage after about nine months. Treating the actuator, valve and temperature condition as separate items would not have addressed the combined failure mechanism.
Engineering Response for Fuel Oil Control
Dombor reviewed the relationship between viscosity, operating temperature, required torque and control response before defining the valve–actuator assembly. The selected 10-inch Class 150 lug-type butterfly valve used a stainless-steel flow path polished to a recorded surface roughness of ≤0.8 μm. The project design records indicate that the revised flow path increased available flow capacity by approximately 20% while reducing areas where viscous fuel could adhere.
Electric heat tracing was fitted around the valve body and connected to a temperature controller. The recorded control range was 80±5°C. Maintaining temperature at the valve helped keep the medium within the intended viscosity range and reduced the risk of local blockage.
A reinforced PTFE seat was selected to reduce friction and support soft-sealing performance in the stated service. The revised sealing arrangement was recorded as providing approximately 30% more sealing pressure, with project leakage data below 0.01% under the applicable test and operating conditions.
The electric actuator included a positioner and continuous feedback to the boiler control system. This allowed the command signal and actual valve position to be compared as load changed. Project records state that the arrangement supported up to five position adjustments per minute without reported drift. For other projects, actuator sizing must still be reviewed against differential pressure, seat torque, temperature, duty cycle and the selected safety factor.
Project-Reported Result
After commissioning, after-sales records show that heavy fuel oil flow variation decreased from more than ±15% to approximately ±2%. Sales follow-up also recorded a 3.5% improvement in boiler thermal efficiency for this installation. These figures describe the measured project result; they are not catalogue ratings for every fuel, boiler or control loop.
The operating interval increased from about nine months to three years. No winter valve failure associated with fuel solidification was reported during the stated follow-up period. Following the initial installation, the same engineering approach was applied to the fuel systems of three boilers at the site.
What This Fuel Oil Control Case Supports
Industrial Butterfly Valves
Leave A Reply
All fields marked with an asterisk (*) are required